MX-6/MX-12系列自動功率因數調整器為適用於 3Φ3W、3Φ4W之產品,在使用時要先依電壓、 頻率、 段數來選擇適當之產品,不可混用。
50Hz 或 60Hz 為不同之產品,請依需求訂購。 額定電壓 220 / 240V 及380 / 415V 需接在不同端子上,MX-12之電壓需要分開指定,請勿錯接,以免燒毀APFR
SPECIFICATION |
MODEL: MX-6 / MX-12 |
Operating Voltage |
230 / 400V, -15% ~ +10% |
Frequency |
50HZ or 60HZ |
Number of Steps |
MX-6: 6 steps, MX-12: 12 steps |
Power Consumption |
10VA max |
Current |
5A (Max.6.5A) with automatic CT polarity detection |
Display |
Power factor, current, current THD (up to 19th harmonic) |
Relay Output |
5A / 250V AC resistive load, 10000 Cycles |
Alarm |
THD Limit, Over / under current, over / under voltage,Over / under power factor, Auto C/K error,
Auto CT polarity detection error |
Switching Sequence |
Automatic / Manual / Programmable |
Closing Sensitivity Delay Time
(for the same step) |
5~600 Sec (5~240 Sec) |
C/K Setting |
0.03~1.20 / Auto |
Power Factor Setting |
0.80 lag ~ 0.80 lead |
Dimensions / Weight |
144 x 144 mm, depth: 91mm, 1kg |
Panel Cut Out |
138 x 138 mm |
Protection Class |
IP54 (frontal) |
Working Temperature
Humidity Range |
-10 ºC~60 ºC, 10% ~ 95%RH |
Standards |
IEC650, IEC348, IEC414, EN61010 |
MX-6/MX-12 中文操作說明書 [點此閱覽]
|